FR-T0400T
Flexematic
4 channels
I/O to internal bus: OptoCoupler Isolation (3KVrms)
Max.1.5mm²(AWG 16)
35mm DIN ruler
Availability: | |
---|---|
Compatiable with FR-ECAT, FR-ENTP, FR-MTCP, FRPFNT couplers
Input Parameter
Channel | 4 channels |
Indicator | 4 input indicators |
Sensor | J / K/ E / T / S / R / B / N / C thermal coupler |
Accuracy | ±0.3%FS, @25℃ ±0.5%FS, @-20~70℃ |
Single Channel Measure Speed | 50Hz (Max) |
Range ℃ | -210~1200℃ J Type |
-270~1370℃ K Type | |
-270~1000℃ E Type | |
-270~400℃ T Type | |
-50~1760℃ S Type | |
-50~1760℃ R Type | |
0~1820℃ B Type | |
-270~1300℃ N Type | |
0~2320℃ C Type | |
Data Type | 16 Bits INT |
Compatiable with FR-ECAT, FR-ENTP, FR-MTCP, FRPFNT couplers
Input Parameter
Channel | 4 channels |
Indicator | 4 input indicators |
Sensor | J / K/ E / T / S / R / B / N / C thermal coupler |
Accuracy | ±0.3%FS, @25℃ ±0.5%FS, @-20~70℃ |
Single Channel Measure Speed | 50Hz (Max) |
Range ℃ | -210~1200℃ J Type |
-270~1370℃ K Type | |
-270~1000℃ E Type | |
-270~400℃ T Type | |
-50~1760℃ S Type | |
-50~1760℃ R Type | |
0~1820℃ B Type | |
-270~1300℃ N Type | |
0~2320℃ C Type | |
Data Type | 16 Bits INT |
Hardware Parameter | Description |
Power | Max.90mA@5.0Vdc |
Isolation | I/O to internal bus:OptoCoupler Isolation(3KVrms) |
Field Power | No |
Wire | Max.1.5mm²(AWG 16) |
Installation | 35mmDIN ruler |
Dimension (H*W*D) | 111*18*76 mm |
Weight | 65g |
Hardware Parameter | Description |
Power | Max.90mA@5.0Vdc |
Isolation | I/O to internal bus:OptoCoupler Isolation(3KVrms) |
Field Power | No |
Wire | Max.1.5mm²(AWG 16) |
Installation | 35mmDIN ruler |
Dimension (H*W*D) | 111*18*76 mm |
Weight | 65g |
Environmental | Description |
Operation Temperature | -20~70℃ |
Ambient Humidity | 5%-95% non-condensing |
Protection Grade | IP20 |
Environmental | Description |
Operation Temperature | -20~70℃ |
Ambient Humidity | 5%-95% non-condensing |
Protection Grade | IP20 |